Video Description
This installation video covers installing the horizontal girts along the sidewalls during the steel-building assembly process. Sidewall girts connect the primary columns and create the supporting framework for the exterior wall panels. Viewers are introduced to consistent spacing, alignment, and secure connections across the length of the wall, making the tutorial useful for both first-time DIY builders and experienced jobsite crews.
What You'll Learn
- How sidewall girts connect the primary columns
- How to maintain consistent spacing and alignment
- How girts support the exterior wall panels
Video Transcript
Now that your main building columns are in place, it’s time to install your sidewall girts.
Girts are the secondary members that will make up the walls of your building.
It’s important to note that in this example, we are using Worldwide Steel Building’s web truss columns and roof trusses with 6-inch purlins on the roof and 3 5/8 inch girts on the walls.
If your building kit has different components than noted, the dimensions you need to use may vary from this video.
Please verify the dimensions with your W drawings.
When installing girts along the sidewall of your building, make sure that you have the correct girt for each location.
Your W drawings and ship list will show you which girts should be used and where they should be placed in your building.
On the galvanized secondary framing list, you will have the location or use for each secondary member.
For the sidewall girts, locate the necessary secondary members that indicate they are for RSW, right side wall, or LSW, left side wall, that pertain to the side wall you are working on. If the girts are identified only as girts at sidewalls, then these girts are used at both sidewalls.
If you have an overhead door framed opening in your walls, then the length of the girts necessary to install will be shown on your W drawings. Refer to our overhead door framing installation video for additional information.
It’s a good idea to check the length of the girt prior to install.
In our example, each sidewall bay is 8 foot 0 inches, and we have no overhead door openings in the walls. Therefore, we are using the girts that are 8 foot 0 inches in length.
Referencing our W1 drawing, we know that the center line of our column is 6 5/8 inches from the edge of the foundation at the end wall.
Measure 6 5/8 inches from the end of your girt to identify the center line of the column and make a mark.
Once marked, place your girt on top of the pre-welded girt clips on the columns.
Because our building has an interior frame, the other end of the girt will stop at the center line of the frame at grid 2.
On your corner column, located at grid one in our example, install 2 number 12 Tek screws through the girt and into the welded clip on the column.
On the frame at grid 2, because the girt stops at the center line of the column, you are only required to install 2 number 12 Tek screws, as shown here.
Continue installing girts using this method until all sidewall girts have been installed. Once completed, it’s time to install your wind rod bracing for the side walls. We’ll see you in the next video.